![Air Circuit Breaker [ACB] - Switchgear components supplier in Bangladesh](https://new.uniquequality-bd.com/wp-content/uploads/2026/01/78805a221a988e79ef3f-768x768.png)
Motor Protection Circuit Breaker [MPCB] / Manual Motor Starter [MMS]
![Motor Protection Circuit Breaker [MPCB] / Manual Motor Starter [MMS] - Switchgear components supplier in Bangladesh](https://new.uniquequality-bd.com/wp-content/uploads/2026/01/motor-protection-circuit-breakers.png)
Manual motor starter with overload and short-circuit protection.
A motor protection circuit breaker (MPCB), also called a manual motor starter (MMS), protects a motor against short circuit, overload and phase loss in one compact device. Its overload setting is adjusted to the motor’s full-load current, and it can switch the motor on and off directly.
Where it is used
- Pumps, fans, blowers and compressors
- Motor feeders in MCC panels, together with contactors
- Machine control panels in garments, textile and food factories
- Small motors started direct-on-line
How to choose
- Setting range that covers the motor’s full-load current from its nameplate.
- Short-circuit breaking capacity for the fault level at the panel.
- Accessories: auxiliary contacts, undervoltage release, enclosure for wall mounting.
- Pairing with a contactor when the motor must be started remotely or automatically.
Why buy from Unique Quality Engineering
Since 2012 we have supplied genuine components from ABB, Schneider Electric, Siemens, Mitsubishi and Fuji Electric to panel builders, factories and contractors across Bangladesh. Our engineers help you choose the right rating and model, and we use the same parts in the panels we build ourselves.
Frequently asked questions
What is the difference between an MPCB and an MCB?
An MCB protects cables, with fixed settings. An MPCB is designed for motors: its overload setting is adjustable to the motor current and it rides through the starting current without tripping.
Do I still need an overload relay with an MPCB?
No. The MPCB already includes thermal overload protection. A separate overload relay is used when protection is provided by fuses or an MCCB with a contactor.
Which MPCB is right for a 7.5 kW motor?
A 7.5 kW, 415 V motor draws about 14–15 A, so choose an MPCB whose setting range includes that current. We can check it from the motor nameplate.
Need a price for an MPCB or manual motor starter? Request a quotation with the rating and quantity, or call or WhatsApp +8801992-389515.
More switchgear components
![Air Circuit Breaker [ACB] - Switchgear components supplier in Bangladesh](https://new.uniquequality-bd.com/wp-content/uploads/2026/01/78805a221a988e79ef3f-768x768.png)
![Vacuum Circuit Breaker [VCB] - Switchgear components supplier in Bangladesh](https://new.uniquequality-bd.com/wp-content/uploads/2026/01/schneider-electric-interruptor-iot-portada-2.png)
![Molded Case Circuit Breaker [MCCB] - Switchgear components supplier in Bangladesh](https://new.uniquequality-bd.com/wp-content/uploads/2026/01/MCCB-1-768x522.jpg)
![Miniature Circuit Breaker [MCB] - Switchgear components supplier in Bangladesh](https://new.uniquequality-bd.com/wp-content/uploads/2026/01/All-Types-of-MCB-miniature-circuit-breaker-ABB-Siemens-Schneider-768x408.jpeg)